Ontario Installation Code for Oil-Burning Equipment (CSA B139 SERIES:19 with 2021 TSSA Ontario Amendments)
This is the tenth edition of CSA B139, Installation code for oil-burning equipment. It supersedes the previous editions published in 2015, 2009, 2004, 2000, 1991, 1976, 1971, 1962, and 1957. The major changes to this edition include - addition of annual visual inspection of fuel oil tank, tubing, piping and fuel oil filters for leakage (CSA B139.1.0 and CSA B139.2); - clarification that the external parts of the body of a fuel-containing device, component, or accessory installed in an oil line has a melting point of not less than 538 °C (CSA B139.1.0); - a new requirement where an external pressure relief valve is installed at an oil pump discharge and downstream of a check valve: – the ullage space of the main tank to which the pressure-relief valve is piped is at least the volume of piping between the check valve and the automatic valve; and – the supply line into the auxiliary supply tank is equipped with a means of anti-siphon where a drop tube is installed (CSA B139.1.0); - the requirements for loop systems have been clarified to apply to elevated installations only (CSA B139.1.0); - a new requirement limiting the acceptance of tanks conforming to API 650 to field erected tanks with capacities that exceed 175 000 L (CSA B139.1.0); - a new requirement applying to auxiliary tanks operating in a continuous overflow condition (CSA B139.1.0); - a new requirement limiting installation storage and supply tanks within tank protection levels II, III, IVA or IVB in buildings of non-combustible construction in conformance with Division B, Part 3 of the National Building Code of Canada (CSA B139.1.0); - a clarification that vent pipes where the opening faces downward without a vent cap is not considered sufficient to prevent the ingress of foreign objects and blockage by ice build-up (CSA B139.1.0); - new requirements have been added for fill pipes or vent pipes recessed into the façade of a building (CSA B139.1.0); - new requirements have been added for through-the wall venting for appliances installed under CSA B139.1.0 (CSA B139.1.0); - new requirements to remove an aboveground or underground tank system that has not been used for more than 3 years (CSA B139.1.0); - new requirements have been added for diesel engines driving fire pumps (CSA B139.1.1); - a new requirement has been added, limiting the operating temperature for an indoor engine supply tank to exceed 38 °C (CSA B139.1.1); - a clarification that engine service rooms require a non-combustible, liquid-tight sill, or ramp to a height corresponding to 10% of the volume of the largest tank in the room, and at least 150 mm (6 in) high (CSA B139.1.1); - new requirements have been added for through-the-wall venting of engine exhausts (CSA B139.1.1); - a new requirement has been added, prohibiting outdoor installation of oil return lines (CSA B139.2); and - new requirements for through-the-wall venting for condensing appliances (CSA B139.2). This Code was prepared by the Technical Committee on Installation of Oil Burning Equipment, under the jurisdiction of the Fuels and Appliances Strategic Steering Committee, and has been formally approved by the Technical Committee. This Code has been developed in compliance with Standards Council of Canada requirements for National Standards of Canada. It has been published as a National Standard of Canada by CSA Group. ------------------------------------------------------------------------------------------------------- CSA B139.1.0:19 - General requirements for large installations Introduction CSA B139 Series, Installation code for oil-burning equipment, is arranged in four parts
This Code specifies minimum requirements for the installation of large oil-burning equipment. Note: The intent of this Code is to apply to multi-unit residential, commercial, institutional, and industrial buildings in accordance with the provincial building code or, in the absence of such regulation, the National Building Code of Canada.
This Code applies to the installation of appliances, equipment, components, and accessories where oil is used for fuel purposes in applications that include
This Code provides minimum requirements for installing or altering all stationary and portable oil- burning equipment, including
Note: For installation of internal combustion engines for emergency power applications, see also CSA C282 and CSA Z32. Both these Standards refer to CSA B139 Series for installation of accessories such as fuel tanks and piping
This Code provides minimum requirements for installing or altering ancillary equipment, including
This Code provides requirements for the maintenance of the most commonly used types of oil-burning equipment.
This Code provides recommended precautions for filling tanks (see Annex I).
This Code does not apply to
Note: For reference, the terms "park model trailers" and "recreational vehicles" are as defined in CAN/CSA-Z241 Series and CSA Z240 RV Series
In this Code, "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Code; "should" is used to express a recommendation or that which is advised but not required; and "may" is used to express an option or that which is permissible within the limits of the Code. Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
The values given in SI units are the units of record for the purposes of this Code. The values given in parentheses are for information and comparison only.
Figures and tables that are referenced with the prefix "B" are to be found in Annex B. Note: For example, a reference in this Code to "Table B.1" means Table B.1 in Annex B. ------------------------------------------------------------------------------------------------------
This Code specifies minimum requirements for the installation of oil-fuelled stationary engines used for
Note: Examples of "building equipment" include air compressors and refrigeration equipment; "industrial equipment" includes pumps, compressors, hoisting equipment; and "emergency equipment" includes fire pumps. This Note does not impose limits on types of driven equipment
The requirements of CSA B139.1.0 apply in addition to this Code. Where a conflict or inconsistency exists between CSA B139.1.0 and this Code, the requirements of this Code shall take precedence.
In this Code, "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Code; "should" is used to express a recommendation or that which is advised but not required; and "may" is used to express an option or that which is permissible within the limits of the Code. Notes accompanying Clauses do not include requirements or alternative requirements; the purpose of a note accompanying a Clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
The values given in SI units are the units of record for the purposes of this Code. The values given in parentheses are for information and comparison only. ------------------------------------------------------------------------------------------------------
This Code applies to the installation of appliances, equipment, components, and accessories where oil is used for fuel purposes in
This Code provides minimum requirements for the field installation of burners and their combustion control systems.
The requirements of CSA B139.1.0 apply in addition to this Code. Where a conflict or inconsistency exists between CSA B139.1.0 and this Code, the requirements of this Code shall take precedence.
In this Code, "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Code; "should" is used to express a recommendation or that which is advised but not required; and "may" is used to express an option or that which is permissible within the limits of the Code. Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
The values given in SI units are the units of record for the purposes of this Code. The values given in parentheses are for information and comparison only. ------------------------------------------------------------------------------------------------------
Where the installation does not meet the restrictions and limitations imposed by this Code, the installation is to be installed in accordance with CSA B139.1.0
This Code applies to the installation of appliances, equipment, components, and accessories where oil is used for fuel purposes in applications that include
Note: The intent of this Code is to apply to residential buildings and small commercial buildings in accordance with the provincial building code or, in the absence of such regulations, in accordance with Part 9 of the National Building Code of Canada
This Code provides minimum requirements for installing or altering all stationary and portable oil- burning equipment, including
This Code provides minimum requirements for installing or altering ancillary equipment, including
Note: Underground fuel oil tank installations of any size and aboveground installations over 2500 L (550 gal) are covered by CSA B139.1.0, CSA B139.1.1, and CSA B139.1.2
This Code provides requirements for the maintenance of the most commonly used types of oil-burning equipment.
This Code provides recommended precautions for filling tanks (see Annex I of CSA B139.1.0).
This Code does not apply to
Note: For reference, the terms "park model trailers" and "recreational vehicles" are as defined in CAN/CSA-Z241 Series and CSA Z240 RV Series
In this Code, "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Code; "should" is used to express a recommendation or that which is advised but not required; and "may" is used to express an option or that which is permissible within the limits of the Code. Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
The values given in SI units are the units of record for the purposes of this Code. The values given in parentheses are for information and comparison only.
Figures and tables that are referenced with the prefix "B" are to be found in Annex B of CSA B139.1.0. Note: For example, a reference in this Code to "Table B.1" means Table B.1 in Annex B of CSA B139.1.0.
Overview The CSA B139 Series
| SDO | CSA: Canadian Standards Association |
| Document Number | |
| Publication Date | Jan. 1, 2021 |
| Language | en - English |
| Page Count | |
| Revision Level | |
| Supercedes | |
| Committee |