1.1 These multi-test methods cover the determination of the oxyhalides—chlorite, bromate, and chlorate, and bromide, in raw water, finished drinking water and bottled (non-carbonated) water by chemically and electrolytically suppressed ion chromatography. The ranges tested using these test methods for each analyte were as follows:

 

Range

Sections

Test Method A:
Chemically Suppressed Ion Chromatography

 

8 to 20

 Chlorite

5 to 500 µg/L

 

 Bromate

1 to 25 µg/L

 

 Bromide

5 to 250 µg/L

 

 Chlorate

5 to 500 µg/L

 

 

 

 

Test Method B:
Electrolytically Suppressed Ion Chromatography

 

21 to 31

 Chlorite

20 to 1000 µg/L

 

 Bromate

1 to 30 µg/L

 

 Bromide

20 to 200 µg/L

 

 Chlorate

20 to 1000 µg/L

 

1.1.1 The upper limits may be extended by appropriate sample dilution or by the use of a smaller injection volume. Other ions of interest, such as fluoride, chloride, nitrite, nitrate, phosphate, and sulfate may also be determined using these test methods. However, analysis of these ions is not the object of these test methods.

1.2 It is the user’s responsibility to ensure the validity of these test methods for waters of untested matrices.

1.3 These test methods are technically equivalent with Part B of U.S. EPA Method 300.1,2 titled “The Determination of Inorganic Anions in Drinking Water by Ion Chromatography.”

1.4 The values stated in SI units are to be regarded as standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard.

1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.

1.6 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.


4.1 The oxyhalides chlorite, chlorate, and bromate are inorganic disinfection by-products (DBPs) of considerable health risk concern worldwide. The occurrence of chlorite and chlorate is associated with the use of chlorine dioxide, as well as hypochlorite solutions used for drinking water disinfection. The occurrence of bromate is associated with the use of ozone for disinfection, wherein naturally occurring bromide is oxidized to bromate. Bromide is a naturally occurring precursor to the formation of bromate.

SDO ASTM: ASTM International
Document Number D6581
Publication Date May 1, 2018
Language en - English
Page Count 23
Revision Level 18
Supercedes
Committee D19.05
Publish Date Document Id Type View
May 1, 2018 D6581-18 Revision
March 1, 2012 D6581-12 Revision
Aug. 15, 2008 D6581-08 Revision
July 10, 2000 D6581-00 Revision
Jan. 1, 2005 D6581-00R05 Reaffirmation