ASTM D2668-07

Current Revision

Standard Test Method for 2,6-<i>di-tert</i>-Butyl-<i> p</i>-Cresol and 2,6-<ital>di-tert</ital>-Butyl Phenol in Electrical Insulating Oil by Infrared Absorption

$83.00

$83.00

$149.40


Sub Total (1 Item(s))

$ 0.00

Estimated Shipping

$ 0.00

Total (Pre-Tax)

$ 0.00


Stay effortlessly up-to-date with the latest standard revisions. When new versions are released, they're automatically charged and delivered to you, ensuring seamless compliance.

Document Preview Not Available...

1.1 This test method covers the determination of the weight percent of 2,6-ditertiary-butyl paracresol (DBPC) and 2,6-ditertiary-butyl phenol (DBP) in new or used electrical insulating oil in concentrations up to 0.5 % by measuring its absorbance at the specified wavelengths in the infrared spectrum.

1.2 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

The quantitative determination of 2,6-ditertiary-butyl paracresol and 2,6-ditertiary-butyl phenol in a new electrical insulating oil measures the amount of this material that has been added to the oil as protection against oxidation. In a used oil it measures the amount remaining after oxidation has reduced its concentration. The test is also suitable for manufacturing control and specification acceptance.

When an infrared spectrum is obtained of an electrical insulating oil inhibited with either of these compounds there is an increase in absorbance of the spectrum at several wavelengths (or wavenumbers). 2,6 ditertiary-butyl paracresol produces pronounced increases in absorbance at 2.72 μm (3650 cm1), and 11.63 μm (860 cm1). 2,6 ditertiary-butyl phenol produces pronounced increases in absorbance at 2.72 μm (3650 cm1) and 13.42 μm (745 cm1).

When making this test on other than a highly oxidized oil or when using a double-beam spectrophotometer, it has been found convenient to obtain the spectrum between 2.5 μm (4000 cm1) and 2.9 μm (3450 cm1) because the instrument is compensated for the presence of moisture and the band is not influenced by intermolecular forces (associations). However, when testing a highly oxidized oil or when using a single-beam instrument better results may be obtained if the scan is made between 10.90 μm (918 cm1) and 14.00 μm (714 cm1).

Increased absorption at 11.63 μm (860 cm1) or 13.42 μm (745 cm1) or both, will identify the inhibitor as 2,6-ditertiary-butyl paracresol or 2,6-ditertiary-butyl phenol respectively (Note 1).

Note 1—The absorbance at 745 cm1 for 2,6-ditertiary-butyl phenol and at 860 cm1 for 2,6-ditertiary-butyl paracresol for equal concentrations will be in the approximate ratio of 2.6 to 1.

SDO ASTM: ASTM International
Document Number D2668
Publication Date Dec. 1, 2007
Language en - English
Page Count 6
Revision Level 07
Supercedes
Committee D27.03
Publish Date Document Id Type View
Dec. 1, 2007 D2668-07 Revision
Oct. 10, 2002 D2668-02E01 Revision
Oct. 10, 2002 D2668-02 Revision
Dec. 10, 1996 D2668-96 Revision
Dec. 1, 2021 D2668-07R21 Reaffirmation
Nov. 1, 2013 D2668-07R13 Reaffirmation