1.1 This specification covers seamless copper water tube suitable for general plumbing, similar applications for the conveyance of fluids, and commonly used with solder, flared, or compression-type fittings. The type of copper water tube suitable for any particular application is determined by the internal or external fluid pressure, by the installation and service conditions, and by local requirements. Means of joining or bending are also factors that affect the selection of the type of tube to be used.

Note 1—Annealed tube is suitable for use with flared or compression fittings, and with solder-type fittings, provided rounding and sizing of the tube ends is performed where needed.

Note 2—Drawn temper tube is suitable for use with solder-type fittings. Types A and B tube, in the drawn temper, are suitable for use with certain types and sizes of compression fittings.

Note 3—This specification is the metric companion of Specification B 88.

1.2 The tube shall be produced from the following coppers, and the manufacturer has the option to supply any one of them, unless otherwise specified:

Copper UNS No. Previously Used DesignationDescription
C10200OFOxygen free without residual deoxidants
C12000DLPPhosphorus deoxidized,low residual phosphorus
C12200DHPPhosphorus deoxidized,high residual phosphorus

1.3 The assembly of copper plumbing or fire sprinkler systems by soldering is described in Practice B 828.

1.4 Solders for joining copper potable water or fire sprinkler systems are covered by Specification B 32. The requirements for acceptable fluxes for these systems are covered by Specification B 813.

1.5 The following safety hazards caveat pertains only to the test methods portion, Section , of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.


This specification covers seamless copper alloy water tubes for general plumbing and similar applications in fluid conveyance. These water tubes made from UNS C10200, C12000, and C12200 copper alloys are commonly used with solder, flared, or compression-type fittings. The materials should be cold-drawn to size and the tubes finished by cold working and annealing to produce the required temper and surface finish. When tubes are furnished in coils, annealing is done after coiling, while those furnished in straight lengths should be in the drawn temper. The numerical values in this specification are not presented in inch-pound units, but rather, in metric or SI units only.


SDO ASTM: ASTM International
Document Number B88
Publication Date Oct. 1, 2005
Language en - English
Page Count 7
Revision Level 05
Supercedes
Committee B05.04
Publish Date Document Id Type View
April 1, 2020 B0088M-20 Revision
March 1, 2018 B0088M-18 Revision
Oct. 1, 2016 B0088M-16 Revision
Oct. 1, 2013 B0088M-13 Revision
Oct. 1, 2005 B0088M-05 Revision
Oct. 1, 2003 B0088M-03 Revision
Sept. 10, 1999 B0088M-99 Revision
April 1, 2011 B0088M-05R11 Reaffirmation