ASTM B280-16

Historical Revision

Standard Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service

$83.00

$83.00

$149.40

$0.00

$0.00

$0.00



Sub Total (1 Item(s))

$ 0.00

Estimated Shipping

$ 0.00

Total (Pre-Tax)

$ 0.00


Stay effortlessly up-to-date with the latest standard revisions. When new versions are released, they're automatically charged and delivered to you, ensuring seamless compliance.

...

1.1 This specification establishes the requirements for seamless copper tube intended for use in the connection, repairs, or alternations of air conditioning or refrigeration units in the field.

Note 1: Fittings used for soldered or brazed connections in air conditioning and refrigeration systems are described in ASME Standard B16.22.

Note 2: The assembly of copper tubular systems by soldering is described in Practice B828.

Note 3: Solders for joining copper tubular systems are described in Specification B32. The requirements for acceptable fluxes for these systems are described in Specification B813.

1.2 The tube shall be produced from the following coppers, and the manufacturer has the option to supply any one of them, unless otherwise specified:

Copper
UNS No.

Previously Used
Designation

Description

 

 

 

C10200

OF

Oxygen free without
  residual deoxidants

C12000

DLP

Phosphorus deoxidized,
 low residual phosphorus

C12200

DHP

Phosphorus deoxidized,
 high residual phosphorus

1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.

1.4 The following hazard statement pertains only to the test method described in 18.2.4 of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.


This specification covers the requirements for seamless UNS C10200, C12000, or C12200 copper alloy tubes used for connection, repairs, or alternations of field air conditioning or refrigeration units. Materials in the form of billets, bars, or tubes should be used to produce a homogeneous uniform wrought structure by either hot or cold working. Each tube should be cold drawn to the finished size and wall thickness. Coiled lengths with soft annealed tempers should be bright annealed after coiling then dehydrated and either capped, plugged, crimped, or otherwise closed at both ends. Straight lengths with hard drawn tempers should be cleaned and either capped, plugged, or otherwise closed at both ends. The grain sizes, tensile properties, and eddy-current and cleanness test results should conform to the values listed herein.


SDO ASTM: ASTM International
Document Number B280
Publication Date April 1, 2016
Language en - English
Page Count 9
Revision Level 16
Supercedes
Committee B05.04
Publish Date Document Id Type View
Oct. 1, 2023 B0280-23 Revision
April 1, 2020 B0280-20 Revision
Oct. 1, 2019 B0280-19 Revision
March 1, 2018 B0280-18 Revision
April 1, 2016 B0280-16 Revision
April 1, 2013 B0280-13 Revision
April 15, 2008 B0280-08 Revision
Oct. 1, 2003 B0280-03 Revision
Oct. 10, 2002 B0280-02 Revision
Sept. 10, 1999 B0280-99E01 Revision
Not Available B0280-95A Revision
Not Available B0280-93A Revision